Activating software updates
Central software updates will be possible via the Device and Update Management Service. You must first activate the service on the System Services page in the WBM.
- Log in to the WBM.
Return to topicHow do I get to the WBM again? Click here for more information...
Establishing a connection to the Web-based Management (WBM):
- Open a web browser on your computer.
- In the address field, enter the URL https://<IP-address-of-the-controller>/wbm,
for example: https://192.168.1.10/wbm.
For further information, see WBM.
- Open the System Services page (Configuration → System Services) in the WBM.
- Activate the checkboxes of the OPC UA Server and the Software Update via Device and Update Management.
- Click the button.
After the PLCnext Control has rebooted, you must enable the port range to be able to communicate with the PROFINET® devices). To do this, proceed as follows:
- Open the Firewall page (Security → Firewall) in the WBM.
- Open the Basic Configuration tab.
- In the Basic Rules section, select Continue from the drop-down list for OPC UA ports in the Action column.
- Click the button.
- Open the User Configuration tab.
- On the Input Rules tab, add a new rule via the .
- Provide the following information:
- Select the interface.
- Select the protocol.
- Enter the IP address range.
- Enter the target port 4840.
- Select the action Accept.
- Click the button.