Secure by default: Resetting with reset type 2

  • Disconnect the power to the controller.
  • Press and hold down the reset button with a non-conductive, pointed object.
  • Hold down the reset button and switch the supply voltage of the controller on.
  • Press and hold the reset button until the STAT LED lights up green. The process takes approx. 40 seconds.
    While the reset button is pressed, the LEDs behave as follows:
    • The CSEC LED starts to light up blue.
    • The STAT LED starts to flash yellow.
    • The STAT LED starts to light up green.
  • Release the reset button as soon as the STAT LED lights up green.
    ↪ All LEDs go out.
    Shortly thereafter, the STAT LED starts to flash red/yellow.
    ↪ The controller is reset with reset type 2 and the recovery system is started.
  • Connect the controller to your PC using a suitable Ethernet cable.
  • Open your web browser.
  • Open the recovery system via the URL http://192.168.1.10.
    If the recovery system does not open:
    Check whether the URL you entered in the web browser actually starts with “http://”.
    The recovery system cannot be opened via an HTTPS connection.
    Please note:
    • As long as the recovery system is active, the LNK and ACT LEDs on the Ethernet interface are switched off (even when the Ethernet connection is active).
    • As long as the recovery system is active, the reset button has no function.

You can perform the following actions in the recovery system: 

  • Install new firmware
  • Restart the controller with the existing firmware

 

 


• Published/reviewed: 2026-01-30 • Revision 020 •